Ferroli boilers manual
Fault F05 generated 5 times within the last 24 hours — possible error with the air pressure switch. Gas valve error — wiring disconnected or faulty gas valve. Card parameter error — possibly wrong card parameter setting. Supply voltage under V — electric mains error. Faulty mains frequency — electric mains error.
Error with system water pressure, possible pressure too low or water pressure switch is damaged. Controller DBM23B error — controller could have an internal error. No burner ignition. No gas or ignition — issue with detection electrode, faulty gas valve or insufficient gas supply pressure.
Flame signal present with burner off. Electrode error or PCB error. Fan error. No V power supply or tachometric signal interrupted fan damaged or out of balance. No flame after the ignition phase. F07 — F14 — A High flue gas temperature. The flue gas probe detects excessive temperature. F08 — A Overtemperature protection intervention.
Heating sensor damaged — no water circulation in the system or air in the system. F09 — A Return sensor damaged — no water circulation in the system or air in the system. F10 — A Flow sensor error. Sensor damaged — wiring shorted or wiring disconnected. F11 — A Return sensor fault. DHW sensor error. F13 — A Flue probe fault. Probe damaged — wiring shorted or wiring disconnected. Flue extraction duct safety device intervention.
Fault F07 generated 3 times in the last 24 hours. Supply voltage under V. Electric mains trouble. Incorrect system water pressure. Pressure too low — water pressure switch either damaged, blocked or not connected. Optional external probe error. Probe damaged or wiring shorted — probe disconnected after activating the outside temperature mode.
Heating sensor damaged, return sensor damaged, no water circulation as air in the system. F42 — A Sensor control protection activation. Heating sensor damaged, return sensor damaged or disconnected. Exchanger protection intervention. No system water circulation — air in system. Printed circuit board PCB parameter fault.
Wrong PCB parameter setting. F56 — A Incorrect parameters electrode damaged or not correctly positioned. F61 — A A54 — A55 — A Boiler chip card BCC service key connected. F68 — A Boiler chip card BCC service key fault. Error loading BCC service key file.
No communication between PCB and gas valve. PCB not connected — valve damaged, replace valve. Maximum number of consecutive resets exceeded. Firmware not loaded successfully. No burner ignition — possible electrode error, defective gas valve or incorrect inlet gas pressure. Flame detected with the burner off — electrode defective main board defective. High limit protection — possible flow temperature sensor not active or incorrectly located, no system circulation. Flue gas fault — fault F07 happened 3 times in the last 24 hours.
Fan error — tachometer signal interrupted for 1 hour or longer. No flame after the ignition phase — electrode error, flame unstable, incorrect valve gas offset or flue gas circuit obstructed.
Flow sensor error — sensor disconnected. Flow sensor error — sensor damaged. High fume temperature — the exchanger probe detects an excessive temperature. Flow sensor error — sensor damaged, short circuited, sensor damaged or wiring broken.
Return sensor error — t-sensor damaged, short circuited, sensor damaged or wiring broken. Exchanger probe error — t-sensor damaged, short circuited, sensor damaged or wiring broken. Flow sensor error — t-sensor damaged, short circuited, sensor damaged or wiring broken.
Fan problem — tachometer signal interrupted fan connection or damaged debris in fan. You need to check and clean fan debris. Supply voltage under v — electric supply error. Irregular mains frequency — electric supply problem. Incorrect system water pressure error — possible sensor damaged or pressure too low. At minimum following points are included in annual service:. Special attention need to be put on all fixings and seals condition that are linked to the room-sealed compartment like grommets, gaskets, grommets, etc.
It is needed because the air leakage would result in pressure drop inside the compartment and would consequently result in tripping the differential pressure switch.
That will cause boiler shut down. After cleaning special attention should also put into verifying the stages of start-up and operation of the pump, thermostats and the gas valve. To repair or parts replacement we advice you to contact directly Ferroli customer service team. Nowadays repairing the parts is not a common practise as new parts are easy to access and are cheap. Ferroli boiler specialist will come with some spare parts from same manufacturer as the original complete boiler to assure the quality and safety.
One year guarantee is provided for all the spares. Before you start to work on Ferroli boilers turn off the thermostat knob and wait till boiler cools down. Isolate the electricity supply, turn off the gas supply at the inlet of the boiler. The cold water mains inlet must be isolated at the inlet cock. The domestic hot water is drained by opening a hot tap. The central heating flow and return cocks should be turned off at the isolation cocks.
Remove the parts following the logical sequence of the instructions below. Replace the part in reverse order.
Always make sure that water and gas washers are in good condition, and when that is not the case- replace as needed. After parts replacement reopen all clocks and recharge the system to about 1 bar, and vent boiler and radiators. Always test for gas soundness of all joints after completing any exchange of gas carrying components and carry out functional checks of controls.
Always test water soundness of all joints, system pressure and the electrical supply. In order to perform any parts replacement you will need to gain general access to the gas appliance- remove outer case. To do so, follow the steps below:. Or re-pressure expansion vessel to the charge value of 0, bar through the C valve. Remove bottom connection from gas valve. Fit top and the bottom gas connections to the new gas valve. Find the water pressure switch and disconnect electrical connections.
You should now note all the positions to the switch. Loosen all the screws should be two fixing the burner assembly to the D combustion chamber of the boiler. The air pressure tubes should now be disconnected from the air pressure switch, its positions should be noted.
Place a piece of cloth or some other absorbent material over rear of control panel to catch any drops of water that may be released when removing the flow meter. Place a piece of an absorbent texitle over the rear of the control panel to catch any drops of water that may fall when the pump head is removed.
Use 4mm allen wrench undo all B allen screws should be four in the head of the pump, Unscrew the pump head from the body. Disconnect the e expansion vessel connecting pipe from the rear of the pump body by removing the clip from the left hand side. Disconnect the return pipe of the boiler and release the pump lower connection by taking away the clip. After each parts replacement you will need to put your boiler back into operation.
In order to start your boiler after parts replacement following steps should be done:. After this all is set you will need to choose which operating mode you want to switch on: central heating and the domestic hot water production or just domestic hot water production- this mode is usually being switched on only during the summer.
The burner will ignite and your appliance will start to operate automatically, controlled by its control and safety devices. If you want to choose the domestic hot water only put the know into summer position. In the hot water mode only your appliance is will operate automatically when the domestic hot water will be drawn off.
When after the start-up procedure correct completion, the burners still fail to ignite resulting in the boiler shut down and the warning lamps will light up, you should wait for about 20 seconds then move the knob to RESET position, hold it for a few seconds and then release it.
The reset electronic control unit will repeat the start-up cycle. In instances where you want to shut down your boiler for a longer period of time weeks and days you should close the boiler isolation gas cock, drain the water from domestic hot water and central heating circuits and turn off the electricity to the boiler. Alternatively, drain the domestic hot water system only and add special anti-freeze to the central heating system.
Ferroli Combi, Modena, Optima, Falkon. Troubleshooting Manual. Safety first! For greater energy savings and bigger comfort it is always advised to use a digital or manual room thermostat Attention! Differential air pressure switch The differential air pressure switch is very important safety device. Frost Protection The frost protection is a safety device which allows boiler to function properly in temperatures close to freezing point. Your boiler needs to be connected to the electricity for the two safety functions above to work to the boiler Boiler cleaning The outer white casing requires just a regular wipe with a soft duster or damp cloth will suffice.
Filling the system with water In the lower temperatures system pressure should be about 1 bar. The maximum output for central heating system adjustment The maximum output for central heating system adjustment should be performed electronically and by P adjustment screw useage starting from a cold central heating system.
You need to verify each time that the urner ignites correctly and that pressure values remain as adjusted or you will need to adjust pressure several times in short time interval The central heating flow temperature adjustment Central heating water temperature is adjusted by rotating the control knob.
The central heating flow adjustment The thermal head is the temperature difference between the delivery water and return water in the central heating circuit. The room temperature adjustment You can control the room temperature by moving the thermostat know to the proper value. Table 1. General fault finding table applicable for all Combi models Fault Action Solution No hot water Is the central heating?
Yes Reset the appliance, if fault stil exists replace the flow meter No central heating Is there hot water? Yes Replace external controls i. Yes Replace C. Yes Replace gas supply, pressure or gas valve No hot water and no central heating Open a hot tap to create a demand — is there a spark at the ignition electrode? Is fan running? Yes Replace air pressure switch or overheat stat if boiler locks out without sparking go to overheat stat No hot water and no central heating Is low water pressure light Flashing?
Yes Top up water to above 1 bar No hot water and no central heating Is fan running? No Replace low water pressure switch Table 2.
No hot water. Is the central heating? Is there a tap symbol on display? Reset the appliance, if fault stil exists replace the flow meter. No central heating. Is there hot water? Replace external controls i. Is the heating demnd lamp on? Replace C. No hot water and no central heating.
Open a hot tap to create a demand — is there a spark at the ignition electrode? Replace gas supply, pressure or gas valve. Replace air pressure switch or overheat stat if boiler locks out without sparking go to overheat stat. Is low water pressure light Flashing?
Top up water to above 1 bar.